Multi-functional condition monitoring sensors
General technical characteristics of the condition monitoring sensors include the following:
1. Mechanical properties/ environmental conditions:
Dimension | 32 x 20 x 10 mm |
IP Rating | IP67, IP68*, IP69K* |
Operating Temperature | 0....70°C |
Weight | 30 g |
Material |
Housing: Stainless steel, Membrane: ePTFE with nylon fleece** |
2. Interface IO-Link Version 1.1:
Speed | COM3 (230.4 kBaud) |
Process data cycle time min. | 10 ms |
3. Display:
2 LEDs in green and orange** |
(Please note: *The specifications refer to the BCM0001; **The specifications refer to the BCM0002)
The important technical features of Balluff's condition monitoring sensors:
- Multiple measurements
- Data preprocessing
- Events/ status indications
- Flexible process data
- Compact design
- Stainless steel housing
- IO-Link interface
- M12 connector
The characteristics of the vibration modules are as follows:
1. Vibration:
- Data acquisition:
Measuring range ± 16 g Resolution 0.5 mg Frequency range 2...3,200 Hz (Sampling rate: 6,400 Hz)
- Data processing:
Vibration velocity
[per measuring axis + magnitude]
RMS, Mean, Standard Deviation, Peak to Peak, Crest Factor, Kurtosis, Skewness Vibration acceleration
[per measuring axis + magnitude]
RMS, Peak to Peak - Data evaluation:
Monitoring of the vibration velocity in our four freely selectable severity zones (based on DIN ISO 10816-3). Configurable thresholds for pre- and main alarms for RMS values of acceleration (a-RMS) or velocity (v-RMS) in three axis and magnitude.
2. Vibration Velocity:
Measuring range RMS | 0...220 mm/s* |
Resolution RMS | 0.42 mm/s* |
Measurement error RMS | ± 5 % FS* |
Linearity deviation RMS | ± 2 % FS* |
3. Vibration Acceleration:
Measuring range RMS | 0...16 g |
Resolution RMS | 0.006 g* |
Measurement error RMS | ± 5 % FS* |
Linearity deviation RMS | ± 2 % FS* |
(Please note: *The quantities are frequency dependent and were determined at a reference of 79.4 Hz.; Statistical values and axis-dependent events (threshold monitoring with pre- and main alarms.)
Below you will find the characteristics of the environmental modules:
1. Temperature:
Measuring range | 0...70 °C |
Resolution | 0.1 °C |
Measurement error | ± 2 % FS* |
Linearity deviation | ± 0.75 % FS* |
2. Humidity:
Measuring range | 5...95 % RH |
Resolution | 1 % RH |
Linearity deviation | ± 2.5 % FS |
(Please note: Due to temperature influences, the evaluation of the absolutely measured variable is not useful. Therefore, the measurement error is not specified. Statistical values (e.g. minimum, maximum) & events (threshold monitoring with lower and upper alarms.)
3. Ambient pressure:
Measuring range | 300...1100 hPa |
Resolution | 0.15 hPa |
Linearity deviation | ± 0.1 % FS |
(Please note: The sensor is designed to detect changes and not to interpret the absolute measured value. For this reason, the measurement error is not specified. Statistical values (e.g. minimum, maximum) & events (threshold monitoring with lower and upper alarms.)